1. Between the auditorium and the stage, a fire curtain is set at the entrance of the stage, which is a special door for safety and fire prevention. In the event of a fire accident in the theater or at the end of each performance, the fire curtain is lowered, separating the stage and the auditorium into two fire zones.
2. In case of emergency, the fire curtain must be able to stay within 45s from the time of release. Fall into place by gravity: when it is 2.5m away from the main stage surface, the damping will start to fall, and the time shall not be less than 10s. An electric lifting device is arranged on the top height of the grid, which can be electrically controlled to rise and manually lowered.
3. A running guide rail is provided on both sides of the fire screen, and a sealing device should be installed around the screen body and the building wall, so that the fire screen can effectively seal the smoke and fire when it is in the descending position.
13305262638
13305262638@163.com
1. Between the auditorium and the stage, a fire curtain is set at the entrance of the stage, which is a special door for safety and fire prevention. In the event of a fire accident in the theater or at the end of each performance, the fire curtain is lowered, separating the stage and the auditorium into two fire zones.
2. In case of emergency, the fire curtain must be able to stay within 45s from the time of release. Fall into place by gravity: when it is 2.5m away from the main stage surface, the damping will start to fall, and the time shall not be less than 10s. An electric lifting device is arranged on the top height of the grid, which can be electrically controlled to rise and manually lowered.
3. A running guide rail is provided on both sides of the fire screen, and a sealing device should be installed around the screen body and the building wall, so that the fire screen can effectively seal the smoke and fire when it is in the descending position.
4. The fire resistance limit of the fire curtain shall meet the international standard and the relevant domestic and local fire protection regulations. The fire screen and guidance system should be able to withstand the pressure difference between the auditorium and the stage.
5. The fire curtain is composed of screen body, guide rail, balance weight, driving device, hoisting system, damping device, etc. It consists of the following parts:
The curtain body is a steel structure frame filled with fireproof and flame retardant materials, which can withstand horizontal and vertical forces
The winding system consists of a motor, a reducer, a brake, a coil, a mechanical manual release assembly, etc. The damping force of the descending damping device is released and the damping position is adjustable. Guide rail and sealing device; Pulley assembly; Counterweight, counterweight frame and guide (if necessary); Wire weaves and fittings.
6. Deep working disc with lift, drop and emergency stop buttons can achieve deep working in situ. The manual release mechanism is arranged on the inside of the platform mouth, and there is operation control and operation status display in the fire control room.
Driving mode | Electric winch with hydraulic damping |
Mode of operation | Electric lift; Electric emergency release drops; Manual emergency release descent |
Lifting current | Power: 5.5kW, current: 11.9A |
Lifting speed | 0~0.15m/s |
Brake | Brake ≥2 |
Drop point | Roll with 2 wire ropes or double branch wire ropes (compound pulley) |
Motor power | ≥5.5kW |
Drum diameter | ≥345mm |
Descent time | During emergency release, the descending time of the full stroke of the curtain body should be between 30s and 45s, and the descending time after 2.5m from the vertical height of the stage surface should not be less than 10s |
Tentorial body | Fire resistance: The fire resistance limit of the curtain body should not be less than 60min |
Horizontal pressure and deformation: When the calculated temperature is 300 ° C, the curtain body should bear a horizontal pressure of 300N/㎡; At this time, the deflection of the main frame of the curtain body is not greater than 1/350 of the calculated span | |
Manual emergency release device | The manual emergency release device shall be installed in an appropriate position on the inside of the platform wall of the opening |
In case of fire emergency, the fire control room should have the function of operating the electric emergency release device | |
Operating performance | Positioning deceleration: can be normal positioning deceleration; Buffer performance: The buffer performance is normal; Operation mode: electric lifting, electric emergency release drop, manual emergency release drop normal |
Protective device | The upper and lower stroke switches and upper limit switches are provided |
Noise | Noise value ≤45dB(A) |